Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM00760
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Provide calculations based on the data shown in Table 403-3, IMC 2000. Reference Section 401, IMC 2000. Third request. |
| 09/26/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The waste and vent riser diagram shows the waste line from a urinal attached to the trap arm of a lavatory. Please revise. 2. Based on the calculations, the ¾" water meter is too small to provide for the new service and produces an excessive pressure drop. Please revise. Reference Section 610.2, UPC 1994. 3. Pipe sizing should be limited to 10 FPS or the maximum values given in the appropriate Installation Standard (e.g. copper piping at 5-8 FPS, PVC at 8 FPS). Reference Section A 6.1, UPC 1994. The 1" cold water lines feeding each battery of water closets are undersized. |
| 10/06/2003 | Doug Williams | ENGINEERING | REVIEW | Approved | |
| 10/14/2003 | Patricia Gehlen | ZONING | REVIEW | Approved | |
| 10/15/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Lights are depicted on Panel L Circuit 2 on the Electric Plan. However, on the Panel Schedule, there are only existing receptacles. Please clarify. 2. Keynote 6 in Library calls for a new lighting fixture. Identify panel and circuit number. 3. Add load calculation on Panel L for new Exhaust Fans on Keynote 3 on Sheet E-101. 4. Line Diagram calls for the installation of #12 G on the load side of a 30A CB. This conductor shall be sized at #10 per NEC Table 250-122. 5. On Sheet E-101, the existing service is depicted as 200A, and scratched out to indicate 400A. Please have the Registrant revise the plans to make this change, and either generate another version resealed, or make use of a Revision triangle, cloud, initial, and date. 6. New AC is line-to-line according to the mechanical plans and panel schedule. If so, the single-pole disconnect indicated on the Electrical Plan will not suffice. 7. Load calculation for service calls for a 2-ton AC. Mechanical Plans and One Line diagram call for a 5-ton AC. Please clarify. 8. What was submitted for electrical was the following: 1) one set with Sheet E-101 sealed 6/15/03 and revised 8/9/03, and Sheet E-102 sealed 6/15/03 and revised 8/9/03 2) a second set with Sheet E-101 sealed 6/15/03 and revised 8/9/03, and no Sheet E-102 3) an isolated Sheet E-102 sealed 9/13/03 This review was based on Sheet E-101 sealed 6/15/03 and revised 8/9/03, and Sheet E-102 sealed 9/13/03. On the next submittal, assemble the plans such that all of the current sheets are in proper order per your index, and that there is no mixing of current with superceded sheets, and that both of the required two sets are complete, and that any superceded sheets are marked as such. 9. Response letter was not dated, items were too general to be able to discern to what they related, and there was no correspondence between numbered responses and original comments (5 comments first review, 11 comments on second review, 6 responses). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/17/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 10/16/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |