Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM00760
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/19/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 02/19/2003 | TACHONG1 | FLOODPLAIN | REVIEW | Approved | |
| 03/11/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/17/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate plumbing plans with waste and vent riser diagram. 2. Correct fixture units and arithmetic on Fixture Connection Schedule. Reference Tables 6-3 and 7-3, UPC. 3. Correct water calculations as required using correct number of fixture units and demand based on supply system predominately for flush valves. Correct pipe sizing as required. Reference Appendix A, UPC. 4. Show riser diagram for utility sink and electric water cooler. 5. Show size, cleanout locations, and routing of existing waste piping. |
| 03/17/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/17/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC. |
| 03/18/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/10/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Identify circuits for all new loads. Specific circuits on the panels, not just a reference to the panel. 2. Submit fixture schedules for all new lighting. 3. Provide Panel schedules for all panels feeding new loads. Show voltage, phase, current, and withstand rating. Circuits feeding new loads shall be depicted as to number of poles and breaker size. Include load calculation for final panel configuration. 4. Total load calculation shall include all new loads. 5. Provide a line diagram for the upgraded service and feeders to panels. Show available fault current at the service, and all other applicable points on the load side. Show bracing of all equipment, as appropriate. |
| 04/21/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Structural Calculations did not include design for the proposed ramp and platform. Note live load to be a minimum of 125 lb. per square foot. Revise calculations 2. Indicate panic hardware at exit doors per section 1003.3.1.9 IBC 3. Provide truss layout for trusses called out within structural calculations. 4. Revise occupant load calculations per Table 1003.2.2.2 IBC. Note stage and lobby/ vestibule areas. 5. Indicate the posting of an occupant load sign per section 1003.2.2.5 IBC. 6. Provide an additional exit in the assembly area per section 1008.2 IBC. 7. Provide approach clearance at nursing door per Figure 404.2.4.1 A117.1 ANSI |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/24/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 04/22/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |