Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM00756
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2003 | JIM EGAN | FIRE | REVIEW | Denied | Indicate fire partition/opening protectives corridor per 2000 IBC Sections 1004.3.2, 708 and Table 714.2. |
| 02/13/2003 | LAITH ALSHAMI | FLOODPLAIN | REVIEW | Approved | |
| 02/21/2003 | DAN CASTRO | ZONING | REVIEW | Denied | Zoning Review Section may not approve the building plans until they have been approved by a structural reviewer. |
| 03/03/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/03/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/03/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/10/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide a rated fire partition with protected openings at common wall of conference room and corridor. Reference section 1004.3.2 IBC. 2. Fire dampers required at supply registers penetrating rated partition |
| 03/12/2003 | GERRY KOZIOL | WWM | REVIEW | Passed | No wastewater plumbing fixtures added. |
| 03/13/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/17/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |