Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T03CM00752
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2003 | JIM EGAN | FIRE | REVIEW | Approved | 1. FIRE HYDRANTS REQUIRED. SUBMIT APPROVED COT WATER PLAN. 2. "HEAVY EQUIPMENT " BUILDING IS NOT B-OCCUPANCY. S-2 REPAIR GARAGE IS MORE APPROPRIATE. SEE 2000 IBC SEC. 406.6.2 FOR MIXED OCCUPANCY SEPARATIONS RELATED TO REPAIR GARAGES. 3. "HEAVY EQUIPMENT" AND "WAREHOUSE" BUILDINGS DO NOT HAVE ADEQUATE EXTERIOR OPENINGS TO COMPLY WITH 2000 IBC SEC. 902.2.12.1. FIRE SPRINKLERS ARE REQUIRED OR ADDITONAL OPENINGS MUST BE PROVIDED. |
| 03/03/2003 | DAN CASTRO | ZONING | REVIEW | Z_DO NOT USE | |
| 03/03/2003 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Z_DO NOT USE | |
| 03/03/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Z_DO NOT USE |