Permit Number: T03CM00740
Parcel: 116122830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00740
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Modify water and waste fixture units in the fixture schedule to conform to the values shown in Sections 610.7 and 703.1, UPC 1994.
2. Coordinate fixture schedule with the plans.
3. Arrange water supply piping to conform to Section 601.2, UPC 1994.
05/19/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/21/2003 TAMI ACHONG OUT TO CUSTOMER Completed