Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM00740
Parcel: 116122830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00740
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Modify water and waste fixture units in the fixture schedule to conform to the values shown in Sections 610.7 and 703.1, UPC 1994.
2. Coordinate fixture schedule with the plans.
3. Arrange water supply piping to conform to Section 601.2, UPC 1994.
4. Correct the water calculations to show a minimum pressure of 15 PSI at the farthest fixture (Section 608.1, UPC) and deduct the pressure drop through only one of the meters (the meters are arranged in parallel).
5. Correct the insulation note in the plumbing specification (Section 2.07); it has symbols substituted for the thickness of the insulation.
04/04/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The Ventilation calculations indicate a total of 375 CFM required for the space. The balancing note calls for only 360 CFM of outside air for the space. The heat pump unit schedule calls for only 150 CFM of outside air for the two heat pumps. Coordinate the balancing note and the heat pump schedule with the calculations. Balance the outside air quantities to each heat pump to ensure that the correct amount of outside air is supplied to each room as shown in the ventilation calculations. Reference Section 403, IMC 2000.
04/23/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/29/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2003 TAMI ACHONG OUT TO CUSTOMER Completed