Permit Number - T03CM00740
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/25/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide equipment data for water heater. 2. Provide detail of water heater installation, including excess pressure relief, expansion tank, recirculation pump, and valves. 3. Provide fixture complete schedule per Sections 610.3 and 703.1, UPC 1994. 4. Provide fixture descriptions for all plumbing fixtures. 5. Complete the waste and vent schematic. 6. Modify waste and vent diagram as required to conform to Sections 706.2 and 707.4, UPC 1994. 7. Clarify which vents are to go through the roof. 8. Provide water riser diagram. 9. Show routing of 1-1/2" CW to meter. 10. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. 11. Show how the building is to be provided with at least one service sink. Reference Table 2902.1, IBC 2000. |
| 02/25/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000. 2. Modify restroom ventilation to conform to Section 403.2.1, exception 3, IMC 2000. 3. Provide size, routing, and termination of condensate drains for air conditioning equipment. Reference Section 307.2, IMC 2000. 4. Provide trap for condensate drains. Reference Section 307.2.4, IMC 2000. 5. Provide 10-feet minimum clearance between outside air openings and plumbing vents or exhaust openings. Reference Section 401.5.1 6. Specify exhaust fans suitable for the intended application. Reference Section 304.1, IMC 2000. |
| 02/28/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/04/2003 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | For BE. |
| 03/10/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. A 60 inch minimum water closet clearance is required. Reference Figure 604.3.1 ANSI A117.1. Revise plan. |
| 03/11/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 03/17/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Indicate wiring method. 2.install disconnecting means at w.heater. 3.Receptacles are missing circuiting. 4. Indicate patient care areas on the electrical plan and specify grounding requirements,as well as the wiring method in these areas. 5. Provide the fault current information on this drawing. 6. Calculate circuit #5 correctly. 7.Provide a fixture schedule with wattages and ballast wattages. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/17/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |