Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM00739
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/02/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The ventilation calculations call for 75 CFM of transfer air to each restroom but exhaust fans (EF-1) are noted as moving only 60 CFM. Introducing 100 CFM into each room pressurizes the restrooms. The exhaust fan schedule still calls out EF-2, instead of EF-1. Resolve these discrepancies. 2. The ventilation calculations call for 168 CFM of outside air for HP-1 but the equipment schedule calls for only 150 CFM for HP-1. Resolve this discrepancy. |
| 04/02/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1) The piping plans for cold water, hot water, and recirculated hot water do not provide enough information to demonstrate that the design conforms to the provisions of the plumbing code. Reference Section 302.3 Uniform Administrative Code. 2) The waste and vent schematics do not match the plumbing plans and both are incomplete. a) Plumbing schematic B shows a 2" drain from the 2-compartment sink but the plans show a 3" drain. b) Plumbing schematic B shows a vent from the first floor joining the 4" drain from the second floor. Reference Section 905.3, UPC. c) The drain lines from P-1, P-2, and FD on plumbing schematics A and B are not sized. d) The wall cleanout shown on plumbing schematic A is 3" but is shown as 4" on the plans. e) The plan view of plumbing schematic B does not connect to the 4" drain line down to the first floor. 3) Modify the water calculations to show a minimum pressure of 15 PSI at the farthest fixture (Section 608.1, UPC) and deduct the pressure drop through only one of the meters (the meters are arranged in parallel). 4) Correct the insulation note in the plumbing specification (Section 2.07); it has symbols substituted for the thickness of the insulation. Reference Section 704.5, IECC. 5) Modify the fixture schedule to agree with the plans and conform to the values shown in Table 6-3 and Table 7-3, UPC. a) Only one 2-compartment sink is shown on the plans. b) The 2-compartment sink has 3 waste fixture units (Public use, Table 7-3). c) The 2-compartment sink has 4 water fixture units (Public use, Table 6-3). 6) Provide controls for the recirculating hot water system to comply with Section 704.6, IECC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/04/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |