Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM00739
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/14/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide equipment data for water heater and recirculating pump. 2. Provide detail of water heater installation, including excess pressure relief, expansion tank, recirculating pump and valves. 3. Show return piping for recirculated hot water for water heater on plans and detail. 4. Provide fixture descriptions for all plumbing fixtures. 5. Clarify reason for supplying hot water to the water closets. 6. Complete the waste and vent schematics. 7. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC. |
| 02/14/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/18/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify which equipment is being installed on this project: HP-1 or HP-2 and EF-1 or EF-2 2. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC. |
| 02/21/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/21/2003 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | Previously approved on 2-12-03. |
| 02/28/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Storage areas over 100 square feet are required to be separated by a one-hour fire partition. Reference table 302.1.1 IBC. Provide location and listing for proposed wall. 2. Conference room is considered an assembly use. Two means of egress is required from the area. Reference sections 302.1 and 1004.2.1 IBC. Revise plans to provide two means of egress from assembly area to exit discharge area. 3. Accessible restrooms are required to have 60 inches of side clearance. Reference figure 604.3.1 ANSI A117.1 4. Provide exit travel plan including accessible routes |
| 03/11/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 03/11/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/21/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |