Review Details: COMMERCIAL TI

Permit Number - T03CM00739
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2003 JIM EGAN FIRE REVIEW Approved
02/14/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide equipment data for water heater and recirculating pump.
2. Provide detail of water heater installation, including excess pressure relief, expansion tank, recirculating pump and valves.
3. Show return piping for recirculated hot water for water heater on plans and detail.
4. Provide fixture descriptions for all plumbing fixtures.
5. Clarify reason for supplying hot water to the water closets.
6. Complete the waste and vent schematics.
7. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC.
02/14/2003 ROBERT SHERRY WATER REVIEW Approved
02/18/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify which equipment is being installed on this project: HP-1 or HP-2 and EF-1 or EF-2
2. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC.
02/21/2003 GERRY KOZIOL WWM REVIEW Approved
02/21/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Approved Previously approved on 2-12-03.
02/28/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Storage areas over 100 square feet are required to be separated by a one-hour fire partition. Reference table 302.1.1 IBC. Provide location and listing for proposed wall.
2. Conference room is considered an assembly use. Two means of egress is required from the area. Reference sections 302.1 and 1004.2.1 IBC. Revise plans to provide two means of egress from assembly area to exit discharge area.
3. Accessible restrooms are required to have 60 inches of side clearance. Reference figure 604.3.1 ANSI A117.1
4. Provide exit travel plan including accessible routes
03/11/2003 PATRICIA GEHLEN ZONING REVIEW Approved
03/11/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2003 CINDY AGUILAR OUT TO CUSTOMER Completed