Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM00738
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/25/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide equipment data for water heater. 2. Provide detail of water heater installation, including excess pressure relief, expansion tank, recirculation pump, and valves. 3. Provide fixture complete schedule per Sections 610.3 and 703.1, UPC 1994. 4. Provide fixture descriptions for all plumbing fixtures. 5. Complete the waste and vent schematic. 6. Modify waste and vent diagram as required to conform to Section 706.2, UPC 1994. 7. Provide water riser diagram. 8. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. |
| 02/25/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/25/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000. 2. Modify restroom ventilation to conform to Section 403.2.1, exception 3, IMC 2000. 3. Provide size, routing, and termination of condensate drains for air conditioning equipment. Reference Section 307.2, IMC 2000. |
| 02/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 4. Provide trap for condensate drains. Reference Section 307.2.4, IMC 2000. 5. Provide 10-feet minimum clearance between outside air openings and plumbing vents or exhaust openings. Reference Section 401.5.1 |
| 02/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000. 2. Modify restroom ventilation to conform to Section 403.2.1, exception 3, IMC 2000. 3. Provide size, routing, and termination of condensate drains for air conditioning equipment. Reference Section 307.2, IMC 2000. |
| 02/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 4. Provide trap for condensate drains. Reference Section 307.2.4, IMC 2000. 5. Provide 10-feet minimum clearance between outside air openings and plumbing vents or exhaust openings. Reference Section 401.5.1 |
| 03/03/2003 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 03/07/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/11/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/13/2003 | DHERRON1 | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/17/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |