Permit Number: T03CM00738
Parcel: 116122830

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM00738
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2003 JIM EGAN FIRE REVIEW Approved
02/25/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide equipment data for water heater.
2. Provide detail of water heater installation, including excess pressure relief, expansion tank, recirculation pump, and valves.
3. Provide fixture complete schedule per Sections 610.3 and 703.1, UPC 1994.
4. Provide fixture descriptions for all plumbing fixtures.
5. Complete the waste and vent schematic.
6. Modify waste and vent diagram as required to conform to Section 706.2, UPC 1994.
7. Provide water riser diagram.
8. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994.
02/25/2003 ROBERT SHERRY WATER REVIEW Approved
02/25/2003 GERRY KOZIOL WWM REVIEW Approved
02/25/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000.
2. Modify restroom ventilation to conform to Section 403.2.1, exception 3, IMC 2000.
3. Provide size, routing, and termination of condensate drains for air conditioning equipment. Reference Section 307.2, IMC 2000.
02/25/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 4. Provide trap for condensate drains. Reference Section 307.2.4, IMC 2000.
5. Provide 10-feet minimum clearance between outside air openings and plumbing vents or exhaust openings. Reference Section 401.5.1
02/25/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000.
2. Modify restroom ventilation to conform to Section 403.2.1, exception 3, IMC 2000.
3. Provide size, routing, and termination of condensate drains for air conditioning equipment. Reference Section 307.2, IMC 2000.
02/25/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 4. Provide trap for condensate drains. Reference Section 307.2.4, IMC 2000.
5. Provide 10-feet minimum clearance between outside air openings and plumbing vents or exhaust openings. Reference Section 401.5.1
03/03/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
03/07/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
03/11/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
03/13/2003 DHERRON1 ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/17/2003 DELMA ROBEY OUT TO CUSTOMER Completed