Permit Number: T03CM00733
Parcel: 117143090

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM00733
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2003 EROSE1 WWM REVIEW Needs Review
08/26/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 1
1. Exterior walls and openings are less than 3 feet from the property line. Walls are required to have a 1-hour fire rating both sides and openings are not permitted. Refs. R302.1, R302.2.

Sheet 2
1. Clarify foundation width in detail 2/2.

Sheet 3
1. A-C wall type does not appear to have been used. Please clarify.


2. Notes reference a footing schedule. No footing schedule was provided. Please clarify.

Sheet 6
1. Mid-height blocking is called out at 8'0" maximum in the typical framing detail. Please revise.


STRUCTURAL COMMENTS
General
1. Provide the lateral analysis and calculations prepared by an Arizona P.E.

2. Provide the engineered truss design prepared by an Arizona P.E.


PLUMBING COMMENTS
Sheet 9
1. Revise gas pipe sizing to comply with UPC 1217.

2. Complete the waste line sizes. Ref. UPC Table 7-5.

3. Show the required cleanouts. Ref. UPC 707.4.


MECHANICAL COMMENTS
Sheet 8
1. Coordinate mechanical equipment specifications with the electrical plan.


ELECTRICAL COMMENTS
Sheet 7
1. Note countertop receptacles as ground fault circuit interrupter protected. Ref. E3802.6.

2. Note garage receptacles as ground fault circuit interrupter protected. Ref. E3802.2.

3. Show disconnect and WP GFI receptacle for rooftop mechanical equipment.

4. Show the oven and range as circuits 2 and 4 as indicated in the panel schedule.

5. Show the location of the heat pump. Coordinate with mechanical.

6. Relocate the convenience receptacles in the study to comply with E3801.2.


7. Circuit 22 does not appear to have been used. Please show as a spare in the panel schedule.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
08/26/2003 EROSE1 WATER REVIEW Needs Review
08/26/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2003 ELAINE ROSE OUT TO CUSTOMER Completed