Permit Number: T03CM00693
Parcel: 110120010

Address:
5330 E GLENN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00693
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Ventilation calculations do not provide for the minimum occupant load specified in Table 403.3. Provide additional outside air or statistical data supporting the stated occupant load. Reference Section 403.3, IMC.
03/26/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/14/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied Storage area still exceeds 100 square feet. Provide one-hour fire barrier as per previous comments number 4,5, &6.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
04/14/2003 ANGIE SHOFFSTALL REJECT SHELF Completed