Permit Number: T03CM00693
Parcel: 110120010

Address:
5330 E GLENN ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM00693
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2003 JIM EGAN FIRE REVIEW Approved
02/25/2003 GERRY KOZIOL WWM REVIEW Passed no fixtures added
02/25/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural analysis of proposed ramp. Note: utilize a minimum of 100 pounds per square foot live load. Reference Table 1607.1 IBC
2. Occupant load for assembly area to be calculated at 7 net not 15. Revise plans.
3. The proposed addition causes the school to be below the minimum number of fixtures required. Revise plans to reflect compliance with Table 2902.1 IBC
4. Provide location and detail for required 1-hour fire barrier for storage areas per Table 302.1.1 IBC.
5. Electrical panel and fire extinguisher cabinet is located within fire barrier walls. Indicate how one- hour firewall integrity is to be maintained.
6. Revise door schedule to reflect required fire rated door assemblies.
7. Provide accessible means of egress required from assembly spaces per section 1003.2.13 IBC.
8. Provide an exit travel plan for the assembly areas.
9. Encroachment into the exit travel by door # 205 is not allowed per section 1003.2.3.1 IBC
02/25/2003 PATRICIA GEHLEN ZONING REVIEW Passed
02/27/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
03/03/2003 ROBERT SHERRY WATER REVIEW Approved
03/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations for sizing of the new natural gas piping. Reference Section 1217.3, UPC.
2. Indicate minimum slope of horizontal rainwater and overflow piping on plans. Reference Appendix D3.3, UPC.
03/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide signature of Principal Envelope Designer on the International Energy Code Compliance form.
2. Indicate location of duct smoke detectors on plans. Reference Section 606.2, IMC.
3. Provide ventilation calculations. Reference Section 403.2, IMC.
03/10/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/17/2003 LISA LESNY OUT TO CUSTOMER Completed