Permit Number: T03CM00689
Parcel: 12201024J

Address:
3900 E GRANT RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T03CM00689
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2003 JAMES TATE FLOODPLAIN REVIEW Approved FUP No. T03OT00201
02/24/2003 JIM EGAN FIRE REVIEW Approved
02/28/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Size MBJ per NEC 250-28 (d). 4/0 Service Entrance Conductors require #2 MBJ, not #4.
2. Size Grounding Electrode conductor to metal water pipe per NEC 250-66. 4/0 Service Entrance Conductors require #2, not #4.
3. Note #12 regarding the removal of ground jumper between the PPS neutral and the PPC ground bus bar. Define PPS. Define PPC. Note by legend refers to Sheet A-5 for definitions. No such definitions on Sheet A-5.
4. Service entrance appears to be in a different location from the meter main on E-3. On E-1 the Meter Main cabinet IS the location of the point of service.
02/28/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Size MBJ per NEC 250-28 (d). 4/0 Service Entrance Conductors require #2 MBJ, not #4.
2. Size Grounding Electrode conductor to metal water pipe per NEC 250-66. 4/0 Service Entrance Conductors require #2, not #4.
3. Note #12 regarding the removal of ground jumper between the PPS neutral and the PPC ground bus bar. Define PPS. Define PPC. Note by legend refers to Sheet A-5 for definitions. No such definitions on Sheet A-5.
4. Service entrance appears to be in a different location from the meter main on E-3. On E-1 the Meter Main cabinet IS the location of the point of service.
03/12/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Provide monopole footing detail
2) Provide structural calc1`s and details of masonary wall. Show wall and reinforcement
details on plans.
03/24/2003 JAY HOGAN OPERATIONS REVIEW Passed
03/27/2003 GLENN MOYER PLANNING-CITY HALL REVIEW Approved 3-27-03 Sheet A-7 Antenna mount plan view shows antennas extending more than one (1) foot and no room has been allowed for downtilt. Drawing must compy with the Zoning Examiner's decision is Special Exception case SE-02-22 condition #3. To ensure compliance show antenna at full downtilt on drawing. Glenn Moyer 791-4541x1167
03/27/2003 GLENN MOYER PLANNING-CITY HALL REVIEW Approved Per revised Sheet A-7

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2003 DELMA ROBEY OUT TO CUSTOMER Completed