Permit Number: T03CM00671
Parcel: 13305054K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00671
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The revised water calculations use a design pressure of 85 PSIG. The water pressure for that area varies from 79 to 86 PSIG according to Tucson Water; base the design of the water piping system on the minimum pressure available. Reference Section 610.7(5), UPC 1994.
2. Update the design pressure drop per 100 feet in the revised water calculations to correspond to the revised pressures. Reference Section 302.3, Uniform Administrative Code 1997.
3. Drawing P2 shows a 1-1/2" water line entering the west side of the building but the Grading, Drainage, & Utility drawing shows a 2" water line entering the north side of the building. Please coordinate these drawings and make the necessary revisions. Reference Section 302.3, Uniform Administrative Code 1997.
06/16/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
6/16/2003
The site plan shows a building size of 13,813. The building plans show a building size of 14,209 square feet. The building plans will require 2 additional parking spaces based on the size yet the site plan only has one excess space. The site plan or building plans must be revised for consistency.
06/16/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2003 TAMI ACHONG OUT TO CUSTOMER Completed
06/16/2003 ANGIE SHOFFSTALL REJECT SHELF Completed