Permit Number: T03CM00671
Parcel: 13305054K

Review Status: Completed

Review Details: SITE

Permit Number - T03CM00671
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The following comment from the previous review has not been addressed.
"The loading areas, if located within 100 feet of an adjacent street, are required to be screened completely from adjacent streets with a minimum six-foot high masonry wall. LUC Table 3.7.2-I"
More specifically, the loading areas must be screened form Broadway Boulevard in compliance with LUC Table 3.7.2-I

2) Parking spaces located adjacent to street landscape borders may not overhang the required ten-foot wide street landscape borders. Revise the plans as necessary to demonstrate compliance. DS 2-06.3.3.E

Resubmittal of revised site and landscape plans is required.
04/25/2003 JOE LINVILLE NPPO REVIEW Denied Please submit a native plant preservation plan or application for exception. LUC 3.8

See http://www.ci.tucson.az.us/dsd/NPPOapp.pdf
for the online version of the form.
05/06/2003 PAUL MACHADO ENGINEERING REVIEW Approved To: Archicon, L.C.
Kevin Garey 4041 N. Central #C-100
Phoenix, Arizona, 85012

SUBJECT: 8711 E. Speedway Blvd.
Site plan T03CM00671 (Second Review)
T14S, R15E, Section 03

RESUBMITTAL REQUIRED: None


Site Plan:

All comments have been addressed. The Site plan is approved. In the future all site requirements must be shown on the site plan. The grading plan and site plan are under separate activity numbers and may be separated in the records department hence not all information will be on the required document. The site plan, grading and SWPPP plans are all attached so it was accepted in this submittal. Please make a note of this for future submittals.


If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate,
05/13/2003 ANY SANITATION REVIEW Approved
05/20/2003 DAN CASTRO ZONING REVIEW Approved
05/21/2003 DAN CASTRO HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2003 LISA LESNY OUT TO CUSTOMER Completed
05/22/2003 ANGIE SHOFFSTALL REJECT SHELF Completed