Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM00671
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/23/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/28/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/28/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | A. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. Please show the location of the RPBP for the building water service on the site utility drawing (a typical installation detail is shown on drawing L-3.0) and include its pressure drop with the water calculations. |
| 05/13/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Lighting Power Calculation has some figures that appear to be erroneous. Fixture Wattages do not conform to those on the Lighting Fixture Schedule Sheet. If a fixture has more than one bulb, its total wattage would have to be greater than that of one bulb. This comment was made on the previous submittal. |
| 05/19/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/20/2003 | DAN CASTRO | ZONING | REVIEW | Denied | Building plans may not be approved until the site plan is approved by all sections and the building plans are approved by structural review. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/23/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 05/22/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |