Permit Number: T03CM00671
Parcel: 13305054K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00671
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2003 GERRY KOZIOL WWM REVIEW Approved
04/28/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/28/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied A. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. Please show the location of the RPBP for the building water service on the site utility drawing (a typical installation detail is shown on drawing L-3.0) and include its pressure drop with the water calculations.
05/13/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Lighting Power Calculation has some figures that appear to be erroneous. Fixture Wattages do not conform to those on the Lighting Fixture Schedule Sheet. If a fixture has more than one bulb, its total wattage would have to be greater than that of one bulb. This comment was made on the previous submittal.
05/19/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/20/2003 DAN CASTRO ZONING REVIEW Denied Building plans may not be approved until the site plan is approved by all sections and the building plans are approved by structural review.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2003 LISA LESNY OUT TO CUSTOMER Completed
05/22/2003 ANGIE SHOFFSTALL REJECT SHELF Completed