| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. City of Tucson requires vertical reinforcement to be positioned prior to pour of footing, not stabbed in place. Revise foundation details, Reference section 1907.5.1 IBC. Note: Stabbing of reinforcement would be allowed if the 3 conditions addressed in section 1907.5.1 IBC are complied with. Reference on plans these conditions. Special inspection shall also be required for this placement. Reference section 1704.13 IBC |
| 10/10/2003 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | Building permit may not be approved prior to site approval. |
| 10/20/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | Site plan approval required prior to building plan approval. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/24/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |