Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM00607
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/24/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/05/2003 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | SUBJECT: 600 West 25th Street REVIEWER: Doug Williams DATE: 5 May 2003 ACTIVITY NUMBER: T03CM00607 SUMMARY: Engineering Division has received the subject submittal on April 24, 2003. Consultation with the Zoning Review Section Supervisor has determined that this project will require a commercial site review. The applicant should refer to Site Plan Content and Specifications requirements in Development Standard 2-02.0 and Development Standard 2-04.0 for Site Plan application and submittal requirements. Until a Site Review Record is completed and submitted, a thorough review cannot be performed by Engineering Division. If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us. Doug Williams Sr. Engineering Division Engineering Division Development Services Department |
| 05/06/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 5/6/2003 Copies of the stamped approved site and landscape plans must be included in the submittal package prior to review and approval. A storage addition is not a tenant improvement. |
| 05/14/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide calculations for proposed masonry wall 2. Is masonry reinforcement to be used to resist anchor bolt withdrawal? Reference Detail G Sheet 6. Please clarify. 3. City of Tucson requires vertical reinforcement to be positioned prior to pour of footing, not stabbed in place. Revise foundation details |
| 05/15/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/31/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 05/15/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |