Permit Number: T03CM00604
Parcel: 123023300

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM00604
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Approved PLAN CHECK COMMENTS - PROJECT #T03CM00604

3/13/03 2609 E. WAVERLY ST.



PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

STRUCTURAL PLANS:

1. 4 X 8 #2 D.F. @ 5 ft. o.c. APPEARS TO BE INADEQUATE TO SPAN 20 ft. AND SHOULDN'T HAVE AN ADDITIONAL LOAD. PLEASE CONFIRM SIZE OF RAFTERS, SPACEING OF RAFTERS, SPAN OF RAFTERS AND PROVIDE COMPOSITION OF SUPPORTING FRAME AND ROOFING.

2. RE-CHECK LAG SIZE.

3. I'VE PHONED LORD & SONS/UNISTRUT TO GET THE SECTION MODULUS AND MATERIAL STRENGTH OF UNISTRUT. CAN YOU EXPEDITE ANY WAY ? ( BONNIE ROBINSON , 1-800-468-3791 )

4. PROVIDE DIMENSIONS OF THE MODULE TO BE USED.

ELECTRICAL PLANS:

1. PLEASE CHECK CONDUIT SIZE FOR SOURCE CIRCUIT.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2003 LISA LESNY OUT TO CUSTOMER Completed