Permit Number: T03CM00594
Parcel: 133240640

Address:
7915 E 3RD ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T03CM00594
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM00594

2/18/03 7915 E. 3rd St.



PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

FOUNDATION PLAN:

1. DETAIL 1/S1 , PLEASE REFERENCE THE DEPTH OF FOOTING FROOM NATURAL GRADE, OR THE CONCRETE SLAB OUTSIDE THE BUILDING.

2. DETAIL 1/S1 , PLEASE SPECIFY THE LENGTH OF THE ANCHOR BOLT.

3. DETAIL 1A/S1 , PROVIDE AN APPROVED SPECIAL INSPECTOR FOR THE EPOXY.

4. PLEASE REMOVE THE WALK FROM THE EASEMENT.

5. DETAIL 3/S1 , LCB POST BASES ARE TO BE FLUSH WITH THE CONCRETE WHICH PUTS THE END GRAIN OF THE POST LESS THAN 1" ABOVE THE FLOOR. SEE R323.1.4 .

6. BRACED WALL SCHEDULE AND DETAILS , THE ANCHOR BOLTS ARE TO BE AT QUARTER POINTS AS OPPOSED TO 16" O.C.

7. WHAT SIZE IS THE PORCH POST FOOTING?






FLOOR PLANS:

1. PROVIDE KEYNOTE 6.6 . SEE THE KITCHEN/HALL DOOR ON THE REFERENCE FLOOR PLAN.

STRUCTURAL PLANS:

1.PLEASE CLARIFY THE CUT THROUGH THE LEDGER IN CLOSET, 107.

2. FRAMING NOTE #7 , PLEASE SPECIFY THE HANGER. ALSO , DTLS. 1 and 5 ON S2.

3. DTL. 4 ON A5 , PLEASE SIZE THE RAFTERS , RIDGE , AND THE PLATES.

SECTIONS - DETAILS - MISC. NOTES:

1. DTL. 3 ON A5 , HOW HIGH ABOVE THE BOTTOM OF THE ROOF DRAIN'S FLOW LINE IS THE BOTTOM OF THE OVER FLOW ?

PLUMBING PLANS:

1. THE WATER CLOSET WASTE FIXTURE UNITS SHOULD BE LISTED AS 6, WHICH IS IN ACCORD WITH THE '94 U.P.C.

ELECTRICAL PLANS:

1. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
02/21/2003 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2003 TAMI ACHONG OUT TO CUSTOMER Completed