Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2003 ELAINE ROSE ZONING REVIEW Needs Review
04/09/2003 EROSE1 FLOODPLAIN REVIEW Needs Review
04/09/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q Provide a special inspection certificate for field welding [2000 IBC Chapter 17].

q Footing F2 in the footing schedule on Sheet S20 is indicated as a 2'-0" wide by 3'-0" long footing, however on the foundation plan the footing is drawn as perfectly square. Please clarify.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-