Permit Number: T03CM00507
Parcel: 13225047B

Address:
4790 S JULIAN AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM00507
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL:

q Where is the handrail for this stair that is shown on the elevation sealed by Daniel Neff (the handrail is noted in the plan view)? The height of the guard is 3'-6" which is correct, however the top of the guard cannot act as the handrail because the top of the handrail needs to be between 34" and 38" [ANSI A117.1 1998 - Sec. 505.4].

q Handrail extensions need to be 12" plus one tread depth beyond the first riser at the bottom of the stairs [ANSI A117.1 1998 - Sec. 505.10.3] (the elevation does not show the additional tread depth extension). At the top of the stairs the handrail needs to extend 12" beyond the last riser [ANSI A117.1 1998 - Sec. 505.10.2] (this extension is not shown on the elevation).

STRUCTURAL:

q There are no structural comments to be addressed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2003 ELAINE ROSE OUT TO CUSTOMER Completed