Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM00507
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL: q Where is the handrail for this stair that is shown on the elevation sealed by Daniel Neff (the handrail is noted in the plan view)? The height of the guard is 3'-6" which is correct, however the top of the guard cannot act as the handrail because the top of the handrail needs to be between 34" and 38" [ANSI A117.1 1998 - Sec. 505.4]. q Handrail extensions need to be 12" plus one tread depth beyond the first riser at the bottom of the stairs [ANSI A117.1 1998 - Sec. 505.10.3] (the elevation does not show the additional tread depth extension). At the top of the stairs the handrail needs to extend 12" beyond the last riser [ANSI A117.1 1998 - Sec. 505.10.2] (this extension is not shown on the elevation). STRUCTURAL: q There are no structural comments to be addressed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/28/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |