Permit Number: T03CM00340
Parcel: 134080860

Address:
8541 E 18TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD

Permit Number - T03CM00340
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
01/24/2003 DAVID RIVERA ZONING REVIEW Approved
02/12/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM00340

2/12/03 8541 E. 18TH ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. PROVIDE HOLD-DOWNS FOR THE BRACED WALL PANELS AT THE EAST AND WEST ENDS OF THE NORTH WALL OF THE NEW FAMILY ROOM. SEE R602.10.6 .


STRUCTURAL PLANS:

1. PLEASE JUSTIFY THE 2-2X6 HEADER OVER THE 7 FOOT WIDE OPENINGS IN THE NORTH WALL OF THE NEW FAMILY ROOM.

2. 2'-8" IS THE LEAST WIDTH A BRACED WALL PANEL MENTIONED IN R602.10.6 . PLEASE JUSTIFY THE 2'-6" WIDE BRACED WALL PANEL SHOWN ON THE FOUNDATION PLAN AT THE EAST END OF THE NORTH WALL.

3. ARE THE ENDS OF THE EXISTING KITCHEN RAFTERS SUPPORTED BY EXISTING STRUCTURE NEXT TO THE ADDITION ?

SECTIONS - DETAILS - MISC. NOTES:

1. DETAILS 4,5, ON 3 , IS A 2ND STORY IS PLANNED, PLEASE INDICATE WHERE . OTHERWISE , PLEASE REMOVE THE REFERENCES TO 2 STORY.

2. DETAIL 12 ON 3 , CLARIFY THE POST ABOVE THE BEAM . INDICATE 2 STORY WHERE APPLICABLE.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLAN EXAMINER: DAVID WITT @ 791-5550 EXT. 1110






2. PROVIDE COMPLETE PLANS AND CAL'CS FOR POST TENSION WALL SYSTEM BY STRUCTURAL ENGINEER REGISTERED IN THE STATE OF ARIZONA.
02/14/2003 JOE LINVILLE NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2003 DELMA ROBEY OUT TO CUSTOMER Completed