Permit Number: T03CM00330
Parcel: 110061160

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T03CM00330
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2003 PETER MCLAUGHLIN NPPO REVIEW Passed
02/12/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM00330

2/13/03 4050 E. HAYHURST LN. #1



PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN: (NOT REQUIRED FOR MODEL PLANS)

1. INDICATE THE LOCATION OF THE SEWER LINE.

2. PROVIDE THE DIMENSION FROM THE "EXISTING HOME" TO THE "PROPOSED CONSTRUCTION" .

FOUNDATION PLANS:

1. FOUNDATION KEYNOTE #2 ; WHERE IS THE "SIMPSON FSA ANCHOR" USED ? FSA's WON'T PROVIDE 1" OF REQUIRED CLEARANCE BETWEEN THE END GRAIN OF A POST AND THE PORCH FLOOR.

2. FOUNDATION KEYNOTE #3 ; WHERE ARE THESE USED ?

3. FOUNDATION KEYNOTE #4 ; THE STEEL ARRANGEMENT DIFFERS FROM DTL. 4 ON PG.1 .

FLOOR PLANS:

1. PLEASE INDICATE HOW THE WINDOWS OPEN .

2. SMOKE DETECTORS ARE REQUIRED TO BE INTER CONNECTED. PLEASE CORRECT THE NOTE THAT SAYS "INTERCONNECTING MAY BE REQUIRED".

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.



4. FIREPLACES: - INDICATE HEARTH SIZE AND MATERIALS, PER R1003.10 OR R1004.2
- FOR FACTORY BUILT OR ZERO CLEARANCE FIREPLACES, PROVIDE CUT SHEETS, MAKE,
MODEL NUMBER AND THE APPROVAL NUMBER OF THE APPROVED TESTING AGENCY
(IE: ICBO #), PER R1002 ALL SHALL COMPLY WITH UL127.
- FOR MASONRY FIREPLACES, SHOW CROSS-SECTION, PER R100.

STRUCTURAL PLANS:

1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD
AND LIVE LOAD.

2. SPECIFY LUMBER GRADE AND SPECIES.

3. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS
CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN
ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. ALSO, THE
ENGINEER OF RECORD SHALL REVIEW AND "SHOP DRAWING" STAMP APPROVAL ON TRUSS CALCULATIONS.

ELEVATIONS:

1. WHAT IS A "TRI-VENT WITH SLR LOUVERS" ? WHAT IS THE NET FREE AREA OF THESE LOUVERS ? PLEASE SPECIFY THE SIZE ON THE PLANS.

2. NOTE AND SPECIFY A COMPLETE ROOFING SYSTEM: ROOFING TYPE, GRADE OF MATERIALS AND METHOD OF
INSTALLATION PER R905.

3. NOTE AND DIMENSION THAT THE FIREPLACE CHIMNEY MUST TERMINATE A MINIMUM OF 2' ABOVE ANY
POINT OF ROOF WITHIN 10' MEASURED HORIZONTALLY AND NOT LESS THAN 3' ABOVE THE POINT WHERE
THE CHIMNEY PASSES THROUGH THE ROOF, PER R1001.6

4. FOAM INSULATION: CLARIFY YOUR COMPLIANCE WITH R318 ON THE MAIN WALLS AND THOSE WALLS TO
THE ATTIC PER R318.2.3.

SECTIONS - DETAILS - MISC. NOTES:

1. ON STANDARD DETAIL SHEETS, CROSS-OUT ALL DETAILS THAT DO NOT APPLY OR WERE NOT USED.

2. DTL. 6/1 ; PLEASE SPECIFY THE LENGTH OF THE ANCHOR BOLTS.

3. DTL. 2,3,4,6,7,8,15,16,25,26,28,39/3 ; WHERE ARE THESE DETAILS USED ? IF NOT USED , PLEASE DELETE.

4. DTL. 14/3 ; PROVIDE DTL. 1/D1 .

5. HOW WILL THE VENT HOLES BREATHE WITH THE OVER HANG STUCCOED ?

PLUMBING PLANS:

1. THE WATER FIXTURE UNIT COUNT SHOULD BE IN CONFORMANCE WITH THE '94 U.P.C.

2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2

3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC.

2. IS NOTE #9 , MECHANICAL PLAN GENERAL NOTES , APPLICABLE ? IF NOT, PLEASE DELETE.


3. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT THE BACK OF THE
DWELLING, PER E3801.7. THIS OUTLET SHALL BE GFI PROTECTED PER E3802.3.

2. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND
SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE
OUTLET, PER E3801.4.1

3. WHERE IS THE SECOND A/C LOCATED ? TWO A/C's ARE LISTED ON THE PANEL SCHEDULE.

4. PROVIDE A SMOKE DETECTOR OUTSIDE THE BEDROOMS AND IN THE IMMEDIATE VACINITY OF THE BEDROOMS.

5. INDICATE THE LOCATION OF CONVENIENCE OUTLET AND LIGHT SWITCH FOR ATTIC HEATING AND AIR
CONDITIONING EQUIPMENT PER E3801.11 AND E3803.4.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110


NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE.
02/14/2003 GERRY KOZIOL WWM REVIEW Approved
02/20/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
02/24/2003 BLANCA ESPINO FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2003 LISA LESNY OUT TO CUSTOMER Completed