Permit Number: T03CM00326
Parcel: 11615190N

Address:
1750 W ANKLAM RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM00326
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
07/03/2003 GP 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
07/07/2003 GERRY KOZIOL WWM REVIEW Approved
07/08/2003 JIM EGAN FIRE REVIEW Denied 1. Medical gas storage room shall conform to 2000 IFC requirements. Indicate/verify conformance on plan. It is not prudent to "field verify all" as indicated on Sht. 1.2.Sec. 3006.2 indicates that the medical gas storage room can be used for no other purpose, including the fire sprinkler riser room.
2. Explain "cryogen" refered to on Sht. E1. Indicate type and amounts of cryogen in use/storage.
3. Indicate ventilation provided for medical gas storage room on plan.
4. Correct note regarding relocation of underground fire sprinkler line on Sht. 2.1. There is no pipe that can be welded, other than stainless steel, that is listed for underground fire service.
07/08/2003 ROBERT SHERRY WATER REVIEW Approved
07/15/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
7/15/2003
Building plans may not be reviewed and approved until the site plan is approved.
07/17/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied Engineering
7/17/2003
Building plans may not be reviewed and approved until the site plan is approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2003 LISA LESNY OUT TO CUSTOMER Completed
07/17/2003 ANGIE SHOFFSTALL REJECT SHELF Completed