Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/24/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
02/05/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
02/10/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Panel X, x-ray feeder is too small for the overcurrent protection. Please correct feeder size or reduce overcurrent protection. |
02/13/2003 | GERRY KOZIOL | WWM | REVIEW | Passed | |
02/14/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
02/14/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/14/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Architectural and Structural plans show AHU-1 as being new. Please provide equipment data for new rooftop unit. 2. Show size, material, routing, and termination of condensate drain for AHU-1. Reference Section 307.2.1, IMC. 3. Provide detail of condensate trap for AHU-1. Reference Section 307.2.4, IMC. 4. Revise air balance of room and rooftop unit to comply with Section 502.4.2, IMC or provide calculations to show compliance with Section 502.4.1, IMC. 5. Show how the location of the intake opening of AHU-1 relative to the exhaust of AHU-1 and exhaust fan EF-4 meet the intent of Section 401.5, IMC. |