Permit Number: T03CM00314
Parcel: 13314227B

Address:
1400 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM00314
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2003 JIM EGAN FIRE REVIEW Approved
02/05/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond
02/10/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Panel X, x-ray feeder is too small for the overcurrent protection. Please correct feeder size or reduce overcurrent protection.
02/13/2003 GERRY KOZIOL WWM REVIEW Passed
02/14/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/14/2003 ROBERT SHERRY WATER REVIEW Approved
02/14/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Architectural and Structural plans show AHU-1 as being new. Please provide equipment data for new rooftop unit.
2. Show size, material, routing, and termination of condensate drain for AHU-1. Reference Section 307.2.1, IMC.
3. Provide detail of condensate trap for AHU-1. Reference Section 307.2.4, IMC.
4. Revise air balance of room and rooftop unit to comply with Section 502.4.2, IMC or provide calculations to show compliance with Section 502.4.1, IMC.
5. Show how the location of the intake opening of AHU-1 relative to the exhaust of AHU-1 and exhaust fan EF-4 meet the intent of Section 401.5, IMC.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2003 DELMA ROBEY OUT TO CUSTOMER Completed