Permit Number: T03CM00302
Parcel: 11307086A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00302
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide fixture unit data and connection sizes (water and waste) for all plumbing equipment. Use Fixture unit data from 1994 UPC; include number of fixtures of each type.
2. Provide water pressure and water pipe sizing calculations. Include water demand from HVAC equipment. Reference Appendix A, UPC.
3. Verify the size of the RPBP connected to the building main complies to Section 610.2, UPC 1994.
4. Complete the Gas Piping Diagram, showing the sizes of all pipe sections. Reference Section 302.3, Uniform Administrative Code 1997.
07/08/2003 MVALDEZ1 ENGINEERING REVIEW Passed
07/08/2003 MVALDEZ1 FIRE REVIEW Passed
07/08/2003 MVALDEZ1 WWM REVIEW Passed
07/09/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approv-Cond
07/09/2003 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed