Permit Number - T03CM00302
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/03/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/03/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide fixture unit data and connection sizes (water and waste) for all plumbing equipment. Use Fixture unit data from 1994 UPC; include number of fixtures of each type. 2. Provide water pressure and water pipe sizing calculations. Include water demand from HVAC equipment. Reference Appendix A, UPC. 3. Verify the size of the RPBP connected to the building main complies to Section 610.2, UPC 1994. 4. Complete the Gas Piping Diagram, showing the sizes of all pipe sections. Reference Section 302.3, Uniform Administrative Code 1997. |
| 07/08/2003 | MVALDEZ1 | ENGINEERING | REVIEW | Passed | |
| 07/08/2003 | MVALDEZ1 | FIRE | REVIEW | Passed | |
| 07/08/2003 | MVALDEZ1 | WWM | REVIEW | Passed | |
| 07/09/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 07/09/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/09/2003 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |