| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate location of cleanout for horizontal drain line on Detail 6/P-1. Reference Section 707.4, UPC. 2. Provide location and sizing information for gutters and downspouts. Reference Appendix D, UPC. |
| 04/01/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide design calculations for exhaust system employing the constant velocity method. Reference Section 510.5, IMC. 2. Provide permanent approved means of access to roof-mounted equipment. Reference Section 306.5, IMC. |
| 04/18/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 4/22/2003 The building plans may not be reviewed and approved until the building plans are approved by the building code reviewer |
| 04/24/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/25/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |