Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM00209
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/17/2003 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 01/31/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/04/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Recirculation of ventilation air from toilet rooms (Office Area and Shop RR) is prohibited. Reference Table 403.3 IMC 2. Coordinate balancing notes on Detail 1/M-2 with Fresh Air Calculations. 3. Coordinate number of RH-1 relief hoods with drawing notes (two shown, "TYP of 3" noted). 4. Provide duct smoke detector for FUR-2. Reference Section 606.2.1 5. Coordinate balancing information for EF-2 shown on Detail 6/M-2 with Equipment Schedule data. 6. Provide combustion air opening for Furnace Room within 12" of Ceiling. Reference Section 703.1.1. 7. Provide material safety data sheets, storage quantities, and expected concentrations of compounds to be utilized in the Glue Booth. 8. Provide additional details of the Glue Booth and clarify the relationship between the Glue Booth and the unit heater, UH. 9. Provide design calculations, duct construction details, and support details for the dust collection system. Reference Sections 510 and 511, IMC. 10. Relocate the dust collector to conform to Sections 511.1.1 and 511.2, IMC. 11. Clarify purpose and geometry of "future duct down to future Selco EB90" |
| 02/04/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water pressure and water pipe sizing calculations. Reference Appendix A, UPC. 2. Recalculate Fixture Units using values from Table 6-3 and 7-3, UPC. 3. Provide upper terminal cleanout near floor sink. Reference Section 707.4, UPC. 4. Indicate location of cleanouts on Detail 3/P-1. 5. Correct scale on Details 2/P-1, and 3/P-1. 6. Coordinate waste line sizing on Plans with sizing on Detail 2/P-2. 7. Provide location and sizing information for gutters and downspouts. Reference Appendix D, UPC. 8. Provide location and size of RPBP assembly. |
| 02/04/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/05/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/14/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/18/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 2/19/2003 Copies of the approved site and landscape plans must be included in the submittal package prior to review and approval |
| 02/21/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide required safety glazing on door and window schedule 2. Provide elevations for accessible restrooms. 3. A structural analysis or an approved manufacturers tables and associated loads is required to be submitted for walls over 20 feet and ceiling joist. 4. A van accessible parking space with an 8-foot loading area is required. Revise plans. Reference section 502.3 ANSI A117.1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/26/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |