Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM00177
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show material, inverts and slope of proposed waste line. |
| 04/23/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 04/23/2004 | TACHONG1 | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/23/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |