Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM00108
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide approved combination fire/smoke dampers for protection of ducts and penetrations of fire resistive ceilings. Reference Section 715, IBC. 2. Show location of smoke detectors and power for combination fire/smoke dampers. 3. Coordinate location of the roof hatch with Structural drawings. 4. Provide calculations for the addition to show compliance to the International Energy Conservation Code, 1998. Please submit the Mechanical Compliance portion of the analysis. |
| 05/21/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 05/30/2003 | DAN CASTRO | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/02/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 05/30/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |