05/07/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide approved combination fire/smoke dampers for protection of ducts and penetrations of fire resistive ceilings. Reference Section 715, IBC.
2. Show location of smoke detectors and power for combination fire/smoke dampers.
3. Coordinate location of the roof hatch with Structural drawings.
4. Provide calculations for the addition to show compliance to the International Energy Conservation Code, 1998. Please submit the Mechanical Compliance portion of the analysis.
05/21/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approv-Cond
05/30/2003 DAN CASTRO ZONING REVIEW Approved