Permit Number: T03CM00108
Parcel: 121136200

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM00108
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Denied Site Plan
1. Indicate all existing and proposed roof slopes and downspouts running under sidewalk. D.S. 2-02.2.1.6
02/04/2003 JIM EGAN FIRE REVIEW Approved
02/13/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Level 1 special inspections to be performed by an approved third party inspection company. Revise general note
2. Floor live load for mezzanine to be a minimum of 125 pounds per square foot per Table 1607.1 IBC. Revise calculations and plans were necessary.
3. Storage room to be separated by a one-hour fire barrier. Provide listed assemblies and locations. Note: bearing walls supporting rated floor ceiling assemblies also to be one hour rated.
4. Mezzanine is required to have one means of egress. Provide a stair detail per section 1003.3.3 and structural calculations complying with Table 1607.1 IBC.
5. Minimum clear room height of 7 feet required for a mezzanine. Reference section 505 IBC. Revise plan
6. Provide an approved guardrail for mezzanine.
02/27/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/27/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/27/2003 DAVID RIVERA ZONING REVIEW Denied Site Plan needs approval prior to Zoning approval of building plans.
02/27/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide approved combination fire/smoke dampers for protection of ducts and penetrations of fire resistive walls and ceilings. Reference Section 715, IBC.
2. Provide access to roof hatch.
3. Provide calculations for the addition to show compliance to the International Energy Conservation Code, 1998.
4. Note on sheet M.1 indicates the mechanical design for this addition was done by B&J Refrigeration. This is in violation of the regulatory provisions of the Arizona Board of Technical Registration: " A registrant shall not sign, stamp or seal any professional documents not prepared by the registrant or a bona fide employee".
02/27/2003 ROBERT SHERRY WATER REVIEW Approved
02/27/2003 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2003 ELAINE ROSE OUT TO CUSTOMER Completed
02/27/2003 ANGIE SHOFFSTALL REJECT SHELF Completed