Review Details: COMMERCIAL NEW

Permit Number - T03CM00059
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2003 JIM EGAN FIRE REVIEW Approved
06/02/2003 GERRY KOZIOL WWM REVIEW Passed
06/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Relocate outside air hood from supply duct to return duct.
2. Provide information on termination of condensate drain to demonstrate compliance with Section 307.2.1, IMC 2000.
06/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/03/2003 ROBERT SHERRY WATER REVIEW Passed
06/17/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS
1) Show location of restrooms. Do they comply to the physically handicapped?
Provide details.
2) Show roof drainage. Show details.
3) Provide stairway construction details, also, details of handrail connections.
06/18/2003 DAVID RIVERA ZONING REVIEW Denied Zoning will approve the building plans upon approval of the plans by the structural reviewers and upon final approval of the site plan.
06/25/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved