Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM00051
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/18/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM00051 DENIED 2/11/04 1. Specify minimum wattages for all lighting fixtures supplied under Specification Note 14, and add that all exterior lighting shall comply with the current Lighting Ordinance. 2. Panel AZBA is listed as 200A on the panel schedule and 100A on the line diagram. Please clarify. 3. Provide Overcurrent Protection for the AZBA feeder. The feeder just comes to the "All-in-One" enclosure and stops. The intent may be to protect it with the hanging 200A main. 4. If the intent is to protect the AZBA feeder with the 200A main, the ampacity on the conductor needs to be increased from #2 to 3/0. 5. If the intent is to protect the AZBA feeder with the 200A main, the grounding conductor needs to be increased from #10 to #6. If the feeder is to be protected by a 100A CB, the grounding conductor should be #8. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/18/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |