Permit Number: T03CM00051
Parcel: 133070010

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM00051
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2003 ANY FLOODPLAIN REVIEW Denied 1. Show limits of 100 year flood plain.
2. Show EHSB per COT sec 26.7.2.
03/11/2003 DAN CASTRO ZONING REVIEW Denied Zoning Review Section may not approve the building plans until the site plan is approved by all sections and the structural reviewer approves the building plans.
03/13/2003 GERRY KOZIOL WWM REVIEW Denied DEQ - Need to show location of septic on plan.
03/21/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Plans indicate an S occupancy. Per the IBC section 312 barns are a U occupancy. Revise plans
2. General notes indicate no field welding, however welded connections are proposed. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2003 LISA LESNY OUT TO CUSTOMER Completed