Permit Number: T03BU03200
Parcel: 12218166A

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU03200
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2004 James Tate ENGINEERING REVIEW Denied DATE: January 6, 2004
ACTIVITY NUMBER: T04BU03200
PROJECT NAME: Kleindale Homes
PROJECT ADDRESS: 3233 E. Kleindale Rd.
PROJECT REVIEWER: James C. Tate, P.E., CFM

The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and floodplain comments have been addressed.

Resubmittal Required: Grading Plan

Grading Plan

1. Specify the number of curb openings at the northwest corner of the property.

2. The plan shows drainage openings in the walls between the lots. Specify size of opening.

3. Show radius of curb returns.

4. Include line and curve data.

5. Identify all walls, curbs, sidewalks, etc.

6. Show finish grades at various points on each lot. Indicate proposed slope percent.

7. The engineers (architects ?) stamp can not be read.

8. Show flow arrows and grades indicating how the drainage from the yards will drain to the rear wall opening.
01/21/2004 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
1/21/2004
Zoning will review and approve the grading plans once Engineering has approved.
01/26/2004 Joseph Linville NPPO REVIEW Denied Submit a native plant preservation plan or application for exception. LUC 3.8

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2004 LISA LESNY OUT TO CUSTOMER Completed