Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03BU03081
Parcel: 137055210

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU03081
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Olive Garden - Lot 5, Westpoint Crossing
DATE: 7 January 2004
ACTIVITY NUMBERS: T03BU03081

SUMMARY: Engineering Section has reviewed the Grading and Drainage and Stormwater Pollution Prevention Plans received on 8 December 2003. Approval of the grading and drainage plan is not recommended at this time. Please address the following comments:

1. Retention/detention basins within the City of Tucson must have a minimum of one maintenance access ramp. The City of Tucson's Standards Manual for Drainage Design and Floodplain Management (Development Standard 10-02.0), Section 14.3.4, states that, "a minimum of one 15-foot wide vehicular access ramp shall be provided into each basin. The maximum roadway or access ramp slope shall not exceed 15 percent. Alternate means of access will be reviewed by the City Engineer on a case-by-case basis". Please depict an appropriate ramp on the grading plan, addressing this requirement.
2. Clearly delineate limits of grading on sheet C-2.
3. There's a note on C-1 referring the reader to sheet C-6 (not in package) - please remove or revise the note, or provide the sheet with each set.
4. Add a general note that grading shall be in conformance with the 2000 International Building Code (IBC) - Local amendment. This is available at: http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf
5. The Grate "INV E" (southwest of the building) is 22.0 on the DP and 20.0 on the Grading plans - please check/revise as necessary.
6. Keynote 12: Please change "guardrail" to barricade railing, per PC/COT SD 105, (unless a guard rail is intended here). Barricade railings are 42" min. in height and are generally acceptable in meeting the "safety barricade" requirements for detention/retention basins.

Please provide a minimum of 2 sets of grading and drainage plans in a resubmittal

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us


Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
01/08/2004 Joseph Linville NPPO REVIEW Denied Include copies of the approved development plan including landscape and native plant preservation sheets. If necessary provide revised plans. Revise landscape plans are to be submitted to the CDRC Office.
12/31/2003 Patricia Gehlen ZONING REVIEW Denied Zoning
1/7/2003
See Engineering comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
01/08/2004 ANGIE SHOFFSTALL REJECT SHELF Completed