Permit Number: T03BU03042
Parcel: 11446023A

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU03042
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2004 Paul Machado ENGINEERING REVIEW Denied To: John Hucko
Landscape Architect
3861 N. First Ave. Tucson, Arizona 85719

SUBJECT: 7575 E. Desert Arbors Street
Grading Plan T03BU03042 (First Review)
T13S, R15E, Section 32

RESUBMITTAL REQUIRED: Grading Plan and Drainage Statement

The Grading Plan (GP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. A separate set of grading plans are required. After approval of the grading plan, one set will filed under the grading permit number, hence the requirement of a separate set of plans.
2. Please submit Grading plans clearly marked "GRADING PLAN" and also showing the entire project site. The Details provided for the Entry/Ramada and the other features are desired.
3. The Grading plan cannot be approved until the Site plan is approved.
4. Please include a response letter to the comments along with the corrected copies with re-submittal.
5. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
6. Please include the area of disturbance to determine Stormwater prevention plan status.
7. List administrative address/site address on plans.
8. Provide a Location Map (3" = 1 mile)
9. Use Engineering Scale only.
10. Show all symbols in the legend.
11. List all Cut and Fill quantities in cubic yards. If both are 0 cy, please list.
12. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. Location of the scuppers are, but not limited to, the asphalt paths and the Ramada area. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
13. Show all limits of grading.
14. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
15. Call out all slopes and stabilization material (concrete, riprap, gabbions or vegetation). Is the rip-rap along Essel Drive existing?
16. Slopes of 3H: 1V require hand placed riprap.
17. Slopes of 2H: 1V or greater require grouted riprap.
18. Cut or fill slopes require a 2' minimum setback from property line.
19. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
20. A Stormwater pollution prevention plan may be required. Contact Paul P. Machado at 791-5550 x1193 for additional information. See note no. 6.

Drainage Statement:

1. A Drainage Statement is required per S.M.D.D.F.M., chap. II, 2.1.3.


If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
01/20/2004 DAVID RIVERA ZONING REVIEW Denied Zoning will approve the grading plan upon approval by Engineering and Landscape Review Sections.
01/23/2004 JOE LINVILLE NPPO REVIEW Denied Submit approved site/landscape/NPP plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed
01/28/2004 ANGIE SHOFFSTALL REJECT SHELF Completed