Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T03BU02984
Review Name: TANKS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/10/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03BU02984 DENIED 2/4/04 1. Lighting shall be computed at 1.25%. 2. 25% shall be added to the load of the highest motor per NEC 430-24. 3. Two sets required for walk-through approvals. |