Permit Number: T03BU02831
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU02831
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2003 James Tate ENGINEERING REVIEW Denied DATE: November 3, 2003
ACTIVITY NUMBER: T03BU02831
PROJECT NAME: Fort Lowell Offices
PROJECT ADDRESS: 2210 E. Fort Lowell
PROJECT REVIEWER: James C. Tate, P.E.

The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and floodplain comments have been addressed.

Resubmittal Required: Grading Plan

GENERAL COMMENTS

1. A copy of the stamped approved Tentative Plat must be included with the Grading Plan submittal.

2. Tentative Plat approval is required prior to Grading Plan approval.

3. The Tentative Plat is currently in the review process. Any changes made to the Tentative Plat must be reflected on the Grading Plan.

GRADING PLAN COMMENTS

1. The Tentative Plat shows a 16' X8" wall opening at Wilson. The Grading Plan Sheet 1 detail 6 specifies 17.5 ft. with no height. The curb inlet and channel are both 19.5 ft. Specifiy the correct height and length of the wall opening on the Grading Plan.

2. Curb returns on Fort Lowell must have a radius of 25 ft.

3. Place a note on the plan that all roof downspouts will be routed under any adjacent sidewalk. Sidewalks must be flood free for up to the ten year event. DS 2-08.4.1.E
11/03/2003 DAN CASTRO ZONING REVIEW Denied Zoning may not approve the grading plan until Engineering has approved the grading plan and the tentative plat has been approved by CDRC.
11/03/2003 PATRICIA GILBERT NPPO REVIEW Denied An approved tentative plat is required prior to grading plan approval.

3 TOS

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2003 DELMA ROBEY OUT TO CUSTOMER Completed
11/03/2003 ANGIE SHOFFSTALL REJECT SHELF Completed