Permit Number: T03BU02830
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU02830
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2004 PATRICIA GILBERT NPPO REVIEW Denied Need a copy of the approved development plan with the grading plan submittal.

Approved Exception 8/15/03 D03-0033
12/17/2003 James Tate ENGINEERING REVIEW Denied DATE: December 18, 2003
ACTIVITY NUMBER: T03BU02830
PROJECT NAME: Sam Hughes Place
PROJECT ADDRESS: 446 N. Campbell
PROJECT REVIEWER: James C. Tate, P.E.

The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and floodplain comments have been addressed.

Resubmittal Required: Grading Plan, Flood Use Permit Application

Grading Plan

1. A copy of the stamped approved Development Plan must be included with the Grading Plan submittal.

2. The Grading Plan must match the Development Plan. The D.P. is currently in the review process. Changes made to the D.P. must be reflected on the Grading Plan.
12/26/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
12/26/2003
Grading plans may not be reviewed and approved until Engineering has approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2004 TAMI ACHONG OUT TO CUSTOMER Completed
01/09/2004 ANGIE SHOFFSTALL REJECT SHELF Completed