Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03BU02401
Parcel: 116274800

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU02401
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: 3492 W. Tiny Bird Court
REVIEWER: Doug Williams
DATE: 23 September 2003
ACTIVITY NUMBERS: T03BU02401 & T03CM03538

SUMMARY: Engineering Division has reviewed the grading plan received on September 22, 2003. Approval is not recommended at this time. Please address the following comments:

SITE/GRADING PLAN COMMENTS
1. Please provide excavation and grading notes on the plan. Include reference to conformance with excavation and grading requirements in accordance with the 2000 International Building Code (IBC), Chapter 36 (local amendment). To access these online, please visit http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf.
2. Please refer to Section 13.1 of the above document (excavation and grading requirements) for placement of fill in excess of 2 feet above existing grade at any location in the outer 100 feet of the developing site. Compliance with items 1-4 must be met prior to approval of the grading plan (2000 IBC). Specifically show how the lower section of the house meets this requirement;
3. Provide a basis of elevation with reference to City of Tucson (COT) Field Book and Page, in accordance with Development Standard (DS) 2-02.2.1.23;
4. Please indicate if rock riprap placement is to be on filter fabric for soil stabilization purposes;
5. Depict and label the 10'x10' utility easement as delineated on the Final Plat (Book 46, Page 8). The plat may be viewed online at the following: http://tdotmaps.transview.org/mandr/mp/mplist.cfm?plan=MP-46-008.

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
10/06/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
10/6/2003
Grading plans will be reviewed and approved once they are approved by Engineering.
10/16/2003 Joseph Linville NPPO REVIEW Needs Review