Permit Number: T03BU02178
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03BU02178
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2004 Paul Machado ENGINEERING REVIEW Approved To: Eduardo Gonazlez
Rick Engineering Company, Inc.
1745 E. River Road, Suite 101
Tucson, Arizona 85718
SUBJECT: East Pointe Commercial Center
Grading Plan T03BU02178 (Third Review)
T14S, R15E, Section 11


RESUBMITTAL REQUIRED: None


Grading Plan:
1. All comments have been addressed. The GP has been approved.

Drainage report:
1. All comments have been addressed. The DR has been accepted.

Stormwater pollution prevention plan:
1. All comments have been addressed. The SWPPP plan has been approved.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
03/12/2004 DAVID RIVERA ZONING REVIEW Approved
03/15/2004 Joseph Linville NPPO REVIEW Approved Revise section B on sheet 3 to remove the 1:1 slope. This is not compatible with the requirement to provide the 20' landscape buffer along the west property line.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/25/2004 LISA LESNY OUT TO CUSTOMER Completed
03/16/2004 ANGIE SHOFFSTALL APPROVAL SHELF Completed