Permit Number: T03BU02009
Parcel: 138180620

Address:
6748 S 6TH AV

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU02009
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2003 Loren Makus ENGINEERING REVIEW Denied DATE: August 25, 2003
TO: Kent Delph, Delph Engineering
SUBJECT: Mitchell Addition Lots 1-4, Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBERS: T03BU02009

SUMMARY: The Grading Plan was reviewed by Development Services Department Engineering Division. The Grading Plan was not approved at this time.

Grading Plan comments:
1) Show Major Streets and Routes (MS&R) right of way including future right of way for 6th Avenue. No development requirements including off-street parking and maneuvering areas can be placed within the future right of way. The MS&R future right of way width is 100 feet.
2) Provide at least one (1) paved permanent access to each lot over terrain which can be traversed by conventional motor vehicles in times of flooding. (Tucson Code 26-8.c) Explain whether the all-weather access will be provided to lots 2 and 3 with paved cross-access easements.
3) Show adequate space for required onsite parking and maneuvering space. Vehicles must be able to turn around on the lots and not back into 6th Avenue.
Revise the Grading Plan to address all of these comments and resubmit two copies for review along with a copy of the approved development plan. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161.

Loren Makus
Senior Engineering Associate
Engineering Division
Development Services
09/15/2003 Daniel Castro ZONING REVIEW Denied Zoning Review
9/15/03
Zoning will review and approve once Engineering has approved the grading plans (and the site plans are approved). Building/garage setback do not appear to meet LUC requirments from a Major Street and Route (6th Ave.)
09/16/2003 JOE LINVILLE NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2003 TAMI ACHONG OUT TO CUSTOMER Completed
09/16/2003 ANGIE SHOFFSTALL REJECT SHELF Completed