Permit Number: T03BU01371
Parcel: 13332027B

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU01371
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2003 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain review, 08/28/2003

Grading Plan:

1. Show roof drainage for all proposed buildings and provide walkway/sidewalk scuppers for roof drains.
2. Show the existing contour lines within the proposed buildings areas in order to determine compliance with the differential grading requirements.
3. Provide the detention basin dimensions and exact location (i.e. stations, distances, etc.). You may include the Horizontal Control Plan as part of the Grading Plan to provide the basin location information.
4. Demonstrate that the detention basin will be graded to provide positive drainage and will not allow any nuisance ponding.
5. The detention basin inlet and maintenance access dimensions shown on sheet 2/3 appear not match the dimensions shown in detail B/3 on sheet 3/3. Revise as necessary.
6. All drainage structures (basins, channels, erosion control structures, etc.) require construction details to allow the contractor to construct them correctly and in the right locations. Revise as necessary.
7. Submit a Geotechnical report that addresses the stability of the proposed slopes.
8. Any work proposed within the 100-year floodplain requires a Floodplain Use Permit (FUP). Submit a FUP application promptly.

If you have any questions, I can be reached at 791-5550 x1159 or lalsham1@ci.tucson.az.us.


Loren Makus, Stormwater Pollution Prevention Plan review, 08/28/2003

The Stormewater Pollution Prevention Plan (SWPPP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

SWPPP Comments:

The following comments that were previously made do not appear to have been adequately addressed
1. Revise the location map to show all receiving waters within one mile of the project. Include the unnamed tributary of Ricardo Small Wash. (Part IV.C.2.3)
2. Revise the location of the silt fence in that appears to be installed within the undisturbed natural area. Silt fence should be installed along a contour. (Part IV.D.2.b)
3. Describe the practice and schedule to routinely remove offsite accumulation of sediment. (Part IV.D.2.c)
4. Describe the velocity dissipation devices that will be used at discharge locations. (Part IV.D.5.b)
5. The operator must sign the SWPPP certification. (Part IV.J.1)

If you have any questions, I can be reached at 791-5550 x1161 or lmakus1@ci.tucson.az.us.
Loren Makus
Senior Engineering Associate

RESUBMITTAL REQUIRED: Revised Grading Plan and Stormwater Pollution Prevention Plan.
09/03/2003 PETER MCLAUGHLIN ZONING REVIEW Denied An approved Development Plan is required prior to grading plan review/approval.
09/03/2003 JOE LINVILLE NPPO REVIEW Denied An approved Development Plan including Native Plant Preservation and Landscape/Mitigation plans are required prior to grading plan review/approval. Submit stamped copies of the plans.

Pre-permit inspections are required prior to any site disturbance. Call 791-5640 Ext. 1140 to schedule inspection when appropriate.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2003 DELMA ROBEY OUT TO CUSTOMER Completed