Permit Number: T03BU01293
Parcel: 14118520C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03BU01293
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2004 Paul Machado ENGINEERING REVIEW Denied To: AMEC
David Martin, PE
3295 W. Ina Road, Ste. 200
Tucson, Arizona 85741
SUBJECT: 9338 E. Old Vail Road
Grading Plan T03BU01293 (Second submittal)
T15S, R15E, Section 27

RESUBMITTAL REQUIRED: Grading Plan and Drainage Report

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. All grading plan comments have been addressed. However the grading plan cannot be approved prior to the approval of the Development plan.
Drainage report:
1. A drainage addendum is not allowed. As per our conversation, you will submit the "whole" drainage report along with your next submittal. The scupper calculations are acceptable, however, the calculations must be included in the DR. Per previous comments.
2. Please see previous comments on the drainage report from the Development plan submittal. See attached.
3. Percolation tests are required prior to the approval of the retention/detention. The rate of percolation cannot exceed 12 hours. Please submit the percolation results on the next submittal.
Stormwater pollution prevention plan:
1. The SWPPP has been accepted.

If you have any questions, I can be reached at 791-5550 x1193 or pmachad2@ci.tucson.az.us
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
02/25/2004 Andrew Connor NPPO REVIEW Denied Submit the approved Native Plant Preservation. The grading plan will be reviewed for consistency with the preservation plan.
03/05/2004 PAUL MACHADO NPDES REVIEW Approved