Permit Number: T03BU01229
Parcel: 136091970

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU01229
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2003 PAUL MACHADO ENGINEERING REVIEW Denied To: TJ Bednar & Co.
4846 N. Davis Avenue
Tucson, Arizona 85705
SUBJECT: 1331 S. Placita Brisa Serena
Grading Plan T03BU01229 (First submittal)
T14S, R15E, Section 24

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies with resubmittal.
2. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
3. List all Cut and Fill quantities in cubic yards.
4. Call out the names of all washes.
5. Call out all slopes and stabilization material (concrete, riprap, gabbions or vegetation).
6. Slopes of 3H: 1V, hand placed riprap is suggested.
7. Slopes of 2H: 1V or greater grouted riprap is suggested.
8. Perhaps a 11"x17" sheet would be a better size for the "Grading/Site" plan.

If you have any questions, I can be reached at 791-5550, or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
06/04/2003 MVALDEZ1 ZONING REVIEW Needs Review
06/04/2003 MVALDEZ1 NPPO REVIEW Needs Review
06/04/2003 PAUL MACHADO NPDES REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
06/04/2003 MONICA VALDEZ REJECT SHELF Completed