Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03BU01216
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/27/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | An approved site plan is required prior to grading plan approval. Please submit an approved copy of the site plan. A pre-permit inspection is required prior to grading plan approval. To schedule call 791-5550, 1118. |
| 07/01/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 7/01/2003 Copies of the approved plot plan must be included in the submittal package prior to review and approval. |
| 07/07/2003 | JOE LINVILLE | NPPO | REVIEW | Denied | A total of 10.128 sq. ft. can be graded per lot. Identify the set-aside area on the plans. A temporary fence is required to preserve the set-aside area for the duration of construction. Clarify the type of revegetation proposed on the plans. |